 ====== How to configure CoreStation with an external wiegand device ====== ====== How to configure CoreStation with an external wiegand device ======
-*If you would like to get basic information about configuration of CoreStation please refer to [[en:​how_to_configure_corestation|]] \\+*If you would like to get basic information about configuration of CoreStationplease refer to [[en:​how_to_configure_corestation|]] \\
  
-In this page, you will be able to learn how to connect an external ​wiegand ​device to CoreStation. And use it for certain operations such as authentication and entrance management with a door.\\+In this article, you will be able to learn how to connect an external ​Wiegand ​device to CoreStations. And use it for certain operations such as authentication and entrance management with a door.\\
  
 <callout type="​primary"​ icon="​true"> ​ <callout type="​primary"​ icon="​true"> ​
Line 11: Line 11:
 </​callout>​ </​callout>​
  
-1. When you take a look at the manual for CoreStation(CS-40),​ you can see a wiring diagram for the product. +1. When you take a look at the CoreStation(CS-40) ​manual, you can see a wiring diagram for the product. 
-[[https://​www.supremainc.com/​sites/all/​themes/​suprema/​images/​products/​corestation/​2.x_CoreStation_IG_V1.00_EN.compressed.pdf|CoreStation Manual]] \\+[[https://​www.supremainc.com/​ko/support/file-download.asp?​iBOARD_CONT_SUB_KEY=303&​sTargetName=Technical_Resources&​sPHYSICAL_NM=20181119151613543.pdf&​sLOGICAL_NM=2.x_CoreStation_IG_V1.00_EN.pdf|CoreStation Manual]] \\
  
 {{:​en:​wiegand_in.png?​nolink&​1000|}} {{:​en:​wiegand_in.png?​nolink&​1000|}}
  
-2. In this example, we will make use of "wiegand ​2" input as well as power supply on this side \\+2. In this example, we will make use of "Wiegand ​2" input as well as power supply on this side \\
  
-3. When you find correct manual for the wiegand ​reader product that you use, you can also find its wiring diagram in it. Wire your wiegand ​reader properly to CoreStation. \\+3. When you find the correct manual for the Wiegand ​reader product that you use, you can also find its wiring diagram in it. Wire your Wiegand ​reader properly to CoreStation. \\
  
-4. So when you wire it correctly you should have the wiring ​setup as below\\+4. When you have wired it correctly you should have the wiring ​set up as below\\
 - TTL Output ports 4&5 will be used for LED & Buzzer - TTL Output ports 4&5 will be used for LED & Buzzer
  
-{{:en:wiegand_reader.jpg?​nolink&​1000|}}+{{:en:final_picture.png?​nolink&​1000|}}
  
-5. Now let's go into BioStar 2, go to Device menu and click Search Device, add the CoreStation device+5. Now let's go to BioStar 2, go to the Device menuand click Search Device, add the CoreStation device
 {{:​en:​corestation_device.png?​nolink&​1000|}} {{:​en:​corestation_device.png?​nolink&​1000|}}
  
-6. Right click on added CoreStation 40, and go "Add Wiegand Device",​ in the new popup window "Add Wiegand Device"​ add "​Wiegand Reader 2." ​+6. Right-click on added CoreStation 40, and click "Add Wiegand Device",​ in the new popup window "Add Wiegand Device"​ add "​Wiegand Reader 2." ​
 {{:​en:​add_wiegand_device.png?​nolink&​1200|}} {{:​en:​add_wiegand_device.png?​nolink&​1200|}}
  
-7. Click on added Wiegand Reader 2and set the settings as you like. If you would like to control LED/Buzzer, you can set it to a certain output. \\ +7. Click on added Wiegand Reader 2 and set the settings as you like. If you would like to control LED/Buzzer, you can set it to a certain output. \\ 
-- In this example, ​because ​Output 4 & Output 5 are close to Wiegand 2 Input, we will assign them to these output ports.+- In this example, ​since Output 4 & Output 5 are close to Wiegand 2 Input, we will assign them to these output ports.
  
 {{:​en:​led_buzzer.png?​nolink&​1200|}} {{:​en:​led_buzzer.png?​nolink&​1200|}}
  
-8. Now go to user, and select a user, in this example the default administrator is selected. Let's click on +Card button on Credential section to assign a card to this user. +8. Now go to the user tab, and select a user, in this example the default administrator is selected. Let's click on the +Card button on Credential section to assign a card to this user. 
  
 {{:​en:​credential.png?​nolink&​1000|}} {{:​en:​credential.png?​nolink&​1000|}}
  
-9. In "​Enroll Card" popup window, please set appropriate Wiegand settings according to the type of card that you will use. The device will scan the card to obtain its card ID information automatically. In our case 26 bit SIA Standard will be used as the card format. \\ +9. In the "​Enroll Card" popup window, please set appropriate Wiegand settings according to the type of card that you will use. The device will scan the card to obtain its card ID information automatically. In our case 26-bit SIA Standard will be used as the card format. \\ 
-1) set Registration Option as "​Register by Card Reader"​ \\ +1) Set Registration Option as "​Register by Card Reader"​ \\ 
-2) set Device as "​Wiegand Reader 2" \\ +2) Set Device as "​Wiegand Reader 2" \\ 
-3) click "Read Card" and scan the device with the card \\ +3) Click "Read Card" and scan the device with the card \\ 
-3) click Enroll. \\+3) Click Enroll. \\
  
 {{:​en:​wiegand_card.png?​nolink&​1000|}} {{:​en:​wiegand_card.png?​nolink&​1000|}}
  
-*Always do not forget to hit "​Apply"​ button on all main menus to take the changes ​in effect.\\+*Do not forget to hit the "​Apply"​ button on all main menus to take the changes ​into effect.\\
  
 {{:​en:​apply.png?​nolink&​1000|}} {{:​en:​apply.png?​nolink&​1000|}}
  
-10. Go to Monitoring menuand click on Real-time log. When you scan the card on the wiegand ​reader, you will be able to see that the wiegand ​reader sends card information to CoreStation for authentication,​ and that authentication is successful with the card ID that we registered for the user. You will also be able to hear the Buzzer sound and see LED lights turn to green when scanning the card.+10. Go to the Monitoring menu and click on the Real-time log. When you scan cards on the Wiegand ​reader, you will be able to see that the Wiegand ​reader sends card information to CoreStation for authentication,​ and that authentication is successful with the card ID that we registered for the user. You will also be able to hear the Buzzer sound and see LED lights turn to green when scanning the card.
  
 {{:​en:​real_time_wiegand.png?​nolink&​1200|}} {{:​en:​real_time_wiegand.png?​nolink&​1200|}}
  
-11. Now let's take this a little bit further. Go to Door menu and click on "Add Door" button. Set it'​s ​appropriate name(in this example we will call it "​Suprema"​). \\+11. Now let's take this a little bit further. Go to the Door menu and click on the "Add Door" button. Set its appropriate name (in this example we will call it "​Suprema"​). \\
 1) Set the entry device as Wiegand Reader\\ 1) Set the entry device as Wiegand Reader\\
 2) Set Door Relay as Relay 2\\ 2) Set Door Relay as Relay 2\\
 3) Set Exit Button and Door Sensor to Supervised Inputs 4&5\\ 3) Set Exit Button and Door Sensor to Supervised Inputs 4&5\\
-4) Set the Open Time, this will dictate how much time you will have between locking and unlocking when relay goes ON and OFF \\+4) Set the Open Time, this will dictate how much time you will have between locking and unlocking when the relay goes ON and OFF \\
  
 {{:​en:​door_config.png?​nolink&​1200|}} {{:​en:​door_config.png?​nolink&​1200|}}
  
-12. Go back to devices and click on CoreStation. Scroll down and expand Advanced taband turn on Supervised Inputs 4&5 as we had set them up for Exit Button and Door Sensor. The resistance can stay as 2.2K Ohms, as they are default. When you hit apply you can see that Supervised Inputs 4&5 will turn on their Green LEDs. \\+12. Go back to devices and click on CoreStation. Scroll down and expand ​the Advanced tab and turn on Supervised Inputs 4&5 as we had set them up for Exit Button and Door Sensor. The resistance can stay as 2.2K Ohms, as they are default. When you hit apply you can see that Supervised Inputs 4&5 will turn on their Green LEDs. \\
  
 *For the reasons why 2.2k Ohms of **circuit resistance** for these **Supervised Inputs** are necessary, please refer to article [[en:​tc_appnote_dm20_wiring_examples|]] *For the reasons why 2.2k Ohms of **circuit resistance** for these **Supervised Inputs** are necessary, please refer to article [[en:​tc_appnote_dm20_wiring_examples|]]
Line 70: Line 70:
 {{:​en:​supervised_inputs.png?​nolink&​1200|}} {{:​en:​supervised_inputs.png?​nolink&​1200|}}
  
-13. Now go back to Monitoring menu -> Real-Time log. Scan the card on the wiegand ​reader. You will now see that not only authentication is successful but also the Door Relay will go ON and OFF, indicating the door being unlocked and locked. You can also notice this by seeing the red LED turning ON and OFF on Relay 2, as well as the tipping sound that is coming from it. The time delay between unlocking and locking will depend on Open Time that you set in step 11. \\+13. Now go back to the Monitoring menu -> Real-Time log. Scan the card on the Wiegand ​reader. You will now see that not only authentication is successful but also the Door Relay will go ON and OFF, indicating the door is being unlocked and locked. You can also notice this by seeing the red LED turning ON and OFF on Relay 2, as well as the tipping sound that is coming from it. The time delay between unlocking and locking will depend on Open Time that you set in step 11. \\
  
 {{:​en:​door_lock.png?​nolink&​1200|}} \\ {{:​en:​door_lock.png?​nolink&​1200|}} \\
  
 ====== Relay work video ====== ====== Relay work video ======
-{{:​en:​lxio6068.mp4?​800x450|}} ​+{{:​en:​lxio6068.mp4?​800x450|}}