BioStar 2.4.0 has an added feature to authorize and control an integrated elevator to stop at different floors. This document will explain the physical integration method and components required for elevator configuration.
The OM-120 is a 12-relay output control module. When used together with BioStar 2, it is able to control the access to select floors from the elevator.
For one controller maximum of 16 OM-120 devices can be connected using a RS-485 daisy chain model, and it also supports AUX input. Furthermore, it can be used together with other features such as Anti-Passback zones, and Fire Zones.
When configuring an elevator with BioStar 2, the three mandatory elements are controller, reader, module.
[BioStar 2 Elevator setting screen]
The physical connections and the features of each device in the elevator control configuration is as below.
With BioStar 2.4.0 one controller is needed per elevator, therefore for four elevators, 4 controllers are required. The physical configuration can be connected as per the image below.
After the physical connection is completed, from BioStar 2 the privilages to each floor and the setting of access groups must be completed for the elevator buttons to be correctly activated.
Click ADD FLOOR LEVEL on the Access Control menu. Select the registered elevator and then select the name of each floor that you wish to configure access privileges. This action is to configure the floor levels that each elevator will be operating.
The elevator setting below is an example of Elevator 1 which operates up to the 6th floor.
[Floor level setting screen]
After the Floor Level is correctly configured, click ADD ACCESS GROUP on the ACCESS CONTROL menu and select the users that are to be given floor levels.
If configured like the image above, the buttons to access the 1st to 6th floor will be initiated for User 000, User 001 and User 002 when using Elevator 1.